SwitchGearis a critical component of power supply and distribution systems, acting as an intermediate station for delivering electrical energy to end-users. Within electrical power system distribution equipment, distribution panels (also called switchgear) are used for power generation, transmission, control, and protection, maintaining normal grid operation. During faults, it promptly disconnects the affected section, and during electrical maintenance, it isolates live equipment. Distribution panels are widely used, responsible for energizing and de-energizing normal circuits, as well as clearing faulted lines. They are indispensable equipment within power systems, playing a vital role in controlling and protecting the safe and stable operation of the national grid and its loads.
The arrangement of distribution equipment and the selection of conductors and electrical apparatus shall satisfy the requirements for normal operation, maintenance, short-circuit, and overload conditions, and shall not endanger personnel safety or surrounding equipment. The insulation level of the distribution equipment shall be coordinated with the rated voltage of the power system. When adjacent live parts within the distribution equipment have different rated voltages, the safe A liberação deve ser determinada com base na tensão classificada mais alta .
Ao selecionar condutores e aparelhos, a umidade relativa utilizada geralmente deve ser a umidade relativa média do mês com a maior umidade local . A tensão de trabalho máxima permitida dos condutores e aparelhos selecionados não deve ser menor que a permissão máxima de operação que não deve ser a mais baixa que o máximo de permissão de operação, que não deve ser o que é mais baixo que o máximo de operação, o máximo que o máximo é o que é mais baixo que o máximo de permissão de operação, o máximo que o máximo é o que é o mais baixo, o que é mais baixo que o máximo de permissão de operação máxima que o máximo de permitir a corrente .}}} circuit. Additionally, their dynamic stability and thermal stability shall be verified under short-circuit conditions. Conductors and apparatus protected by fuses may be exempt from thermal stability verification but dynamic stability verification is still required. For conductors and apparatus protected by high-voltage current-limiting fuses, dynamic and thermal stability verification can be Realizado com base nas características do fusível limitador de corrente . para circuitos de transformador de tensão protegidos por fusíveis, a verificação da estabilidade dinâmica e térmica pode ser omitida .
When determining the short-circuit current, the calculation shall be based on the normal system configuration likely to produce the maximum short-circuit current, taking into account the power system's 5–10 year development plan and the project's own plan. When calculating the short-circuit point, the location where the short-circuit current is the highest under normal system configuration shall be selected. For 6kV or 10kV outgoing feeders Equipado com reatores, os leads e buchas localizadosantesA barreira (no lado da linha do reator) deve ser calculada assumindo que o ponto de curto-circuito éa montantedo reator . leads e aparelhos localizadosdepoisA barreira (no lado da carga do reator) geralmente é calculada assumindo que o ponto de curto-circuito éa jusantedo reator .